Nexans XKDT-YT Alu XLPE insulated 3 core cables

Products

XKDT-YT 3x1x 95 Alrm / 16 CuK mm² 12/20kV

Nexans ref. 10152610

  • Packaging: Cut to length (m)
  • Conductor cross-section: 95 mm²
  • Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km

 

XKDT-YT 3x1x150 Alrm / 25 CuK mm² 12/20kV

Nexans ref. 10152611

  • Packaging: Cut to length (m)
  • Conductor cross-section: 150 mm²
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km

 

XKDT-YT 3x1x240 Alrm / 35 CuK mm² 12/20kV

Nexans ref. 10152613

  • Packaging: Cut to length (m)
  • Conductor cross-section: 240 mm²
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km

 

XKDT-YT 3x1x300 Alrm / 35 CuK mm² 12/20kV

Nexans ref. 10217446

  • Packaging: Cut to length (m)
  • Conductor cross-section: 300 mm²
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km

 

XKDT-YT 3x1x400 Alrm / 35 CuK mm² 12/20kV

Nexans ref. 10182717

  • Packaging: Cut to length (m)
  • Conductor cross-section: 400 mm²
  • Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km

 

Description

Description

Standards

  • Product
    HD 620; IEC 60502
  • National
    ASE

Applications

  • Underground distribution networks
  • Laying in tubes and direct buried
  • Arises in electrical substations

Construction

  • Aluminium conductor
  • Inner Semiconductor
  • Cross-linkend PE insulation (XLPE)
  • Outer semi-conductor
  • Semi-conductive swelling tape
  • Copper wire screen
  • Swelling tape
  • Outer PE sheath
  • Assembly of 3 XLPE insulated single core cables
  • Outer HDPE-sheath

admissible load MV cables

 

Currents are indicative and given for normal service conditions.

  •  Permanent charge 24h at 100% LF =1.0
  • Conductor temperature 90 ° C

 

For cable laid in earth in tubes

  • Depth of laying in soil : 1.0 m
  • Max. soil temperatureempérature : 20 °C
  • Soil thermal resistivity: 1.0 °C m/W

 

For cables placed in the open air

  • Max. air temperature : 30 °C 
  • Protected from direct sunlight
  • laid on consoles or cable trays

  

Grounding:

  • at one end, in this case the induced voltage increases proportionally with the length of the
    the link.

    Attention, too high induced voltage can cause a breakdown of the outer sheath during overvoltages
    transient.

  • Either at both ends, which generates circulating currents and therefore more or less acceptable losses..

 

Correction factor

If the terms of service differ from those set out above, allowable currents must be corrected
taking into account all the correction factors that apply to the installation and service conditions encountered.


Main factors to consider are the following:

 

  • Variable load, factor taking into account variable load, 10h to 100% and 14h to 60% LF= 0.627
  • Operating temperature
  • Ambient Temperature
  • Thermal soil resistivity, factor taking into account the thermal resistivity of the soil in [°C * m / W]
  • Magnetic armor


Our engineers are at your disposal to help and advise you.

Characteristics

Characteristics

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12/20 kV
Maximum operating voltage
24 kV

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close