AMV-J-AFN 24.4/400-630SM16(3)

Description

Description

Standards

  • Test
    HD 629.1 S2

Prefabricated, factory-tested end closure body with integrated field control. Conductor and shield connection, sealing material, assembly aid and assembly instructions


When ordering, specify:
• Type of cable
• Diameter over insulation
• Screen construction, desired shield connection
• Conductor cross-section, material and class

 

To be ordered separately:
• Earth connection for ribbon or pipe shield
• Fixing Bride
• Distribution cap for three-conductor cable
• Terminal for connection to overhead line

Design AMV-J-AFN

Product description

Cable lug for termination AFN

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Technology
Slip-0n
Conductor material
Copper or Aluminum
Insulation
Synthetic
Material of the outer core / screen
Copper wires
Insulating material
Silicone
Type of conductor
Circular, solid or stranded
Type of bolt
Lug

Dimensional characteristics

Dimensional characteristics

Diameter over insulation, range
34 ... 46 mm
Conductor cross-section, range
400 ... 630 mm²
Length "L"
405.0 mm
Outer Diameter
118 mm
Number of sheds
4
Approximate weight per set
2.2 kg

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Maximum operating voltage
24 kV
Maximal partial discharge at 2Uo
10 pC
Impulse voltage
125 kV
Flashover distance
405 mm
Nominal leakage path
462 mm

Usage characteristics

Usage characteristics

Field of application
Outdoor
Packaging
3 pieces set

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.