AMV-J-AINE 24.6/1200SM20(3)

Description

Description

Standards

  • Test
    EN 61442; HD 629.1 S2

AMV-J-AIN

Cable lug for termination AIN

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Material of the outer core / screen
Copper or aluminium tape
Technology
Slip-0n
Material
-
Type of conductor
Circular, solid or stranded
Conductor material
Copper or Aluminum
Insulation
Synthetic
Type of bolt
Lug

Dimensional characteristics

Dimensional characteristics

Diameter over insulation, range
46 ... 58 mm
Conductor cross-section, range
1200 ... 1200 mm²
Length "L"
405.0 mm
Outer Diameter
98 mm
Number of sheds
7
Approximate weight per set
4.5 kg

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Maximum operating voltage
24 kV
Maximal partial discharge at 2Uo
10 pC
Impulse voltage
125 kV
Flashover distance
405 mm

Usage characteristics

Usage characteristics

Field of application
Indoor
Packaging
3 pieces set