Cable HS XKDCu(Al)T 1000 mm² Cu 150 kV

Description

Description

Standards

  • Test
    IEC 60840; IEC 62067
  • National
    HD 632 Section O

Applications

  • Underground distribution networks
  • Pipe laying and ground laying
  • Installation in electrical substations

These products are manufactured according to your specifications. Therefore, there is no standard product list. For more information, please contact us.

 

Construction

  • Copper or aluminum conductor
  • Extruded inner semi-conductor
  • Cross-linked PE insulation (XLPE)
  • Extruded outer semi-conductor
  • Semi-conductive swelling tape
  • Metal shielding
  • Semi-conductive swelling tape
  • Radial sealing (copper or aluminum tape)
  • Outer HDPE sheath

Properties

  • Longitudinal and radial sealing provided by two layers of tapes that swell in the presence of moisture and prevent the spread of water in case of injury to the sheath
  • Special abrasion resistant PE outer jacket with low shrinkage rate
  • Cross-linked PE insulation (XLPE) with high dielectric strength and low losses
  • Halogen free

Characteristics

Characteristics

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
1000 mm²
Conductor diameter
39.1 mm
Diameter over insulation
79.5 mm
Outer Diameter
93 mm
Screen section
95 mm²
Approximate weight
15.2 kg/m

Electrical characteristics

Electrical characteristics

Operating voltage
150 kV
Permissible short circuit current screen 1s
15.0 kA
Permissible short circuit current conductor 1s
143 kA
Max. DC resistance of the conductor at 20°C
0.018 Ohm/km
Capacity core to screen
0.218 pF/m
I max. @ 90°C-buried in trefoil joined
1145 A
I max. @ 90°C-buried in trefoil spaced
1180 A
I max. @ 90°C-buried in flat formation joined
1030 A
I max. @ 90°C-buried in flat formation spaced
1175 A
I max. @ 75°C-buried in trefoil joined
1025 A
I max. @ 75°C-buried in trefoil spaced
1055 A
I max. @ 75°C-buried in flat formation joined
920 A
I max. @ 75°C-buried in flat formation spaced
1050 A
Load factor
1
Sheaths grounding
1 point
Thermal soil resistivity dry zone
0.85 °K.m/W

Mechanical characteristics

Mechanical characteristics

Maximum tensile load during service (Tl)
4000.0 daN

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Ambient ground temperature
20 °C
Laying operation bending radius
3300 mm
Laying depth, center of system
1000 mm
Laying tube diameter
150 mm
Distance between tubes (X)
220 mm

Resources

Resources

Documentation

Construction pdf — 292.1 kB

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close