Cable HS XKDCu(Al)T 1000 mm² Alu 150 kV
Cable HS XKDCu(Al)T 1000 mm² Alu 150 kV
HV XLPE insulated single core cables with a copper wire screen, longitudinal and radial watertightness.
Read more- Nexans ref. : XKDCu(Al)T 1000 Alu 150 kV
Description
Description
Standards
-
TestIEC 60840; IEC 62067
-
NationalHD 632 Section O
Applications
- Underground distribution networks
- Laying in tubes and directly buried
- Arises in electrical substations
Key points
- Low shrinkage, abrasion-resistant PE outer sheath
- Longitudinal watertightness by swelling tapes which prevent water ingress in case of damage to the outer sheath
- Low loss high dielectric strength XLPE insulation
Construction
- Aluminium conductor
- Inner semi-conductor
- Cross-linkend PE insulation ( XLPE )
- Outer semi-conductor
- Semi-conductive swelling tape
- Copper wire screen
- Semi-conductive swelling tape
- Metallic sheath lengthwise (Copper or Aluminium)
- Outer PEHD sheath
Comment
- Cross section from 240 mm² to 2000 mm²
- Other level's tension or cross-section on request
- NOflamm version available on request
- 2 metallic sheaths lengthwise available: copper XKDCuT, Alu XKDAlT
Characteristics
Characteristics
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
1000 mm²
Conductor diameter
38.8 mm
Diameter over insulation
79.5 mm
Outer Diameter
93 mm
Screen section
95 mm²
Approximate weight
9 kg/m
Electrical characteristics
Electrical characteristics
Operating voltage
150 kV
Permissible short circuit current screen 1s
15.0 kA
Permissible short circuit current conductor 1s
94 kA
Max. DC resistance of the conductor at 20°C
0.029 Ohm/km
Capacity core to screen
0.223 pF/m
I max. @ 90°C-buried in trefoil joined
980 A
I max. @ 90°C-buried in trefoil spaced
1010 A
I max. @ 90°C-buried in flat formation joined
875 A
I max. @ 90°C-buried in flat formation spaced
1000 A
I max. @ 75°C-buried in trefoil joined
880 A
I max. @ 75°C-buried in trefoil spaced
905 A
I max. @ 75°C-buried in flat formation joined
785 A
I max. @ 75°C-buried in flat formation spaced
900 A
Load factor
1
Sheaths grounding
1 point
Thermal soil resistivity dry zone
0.85 °K.m/W
Mechanical characteristics
Mechanical characteristics
Maximum tensile load during service (Tl)
2000.0 daN
Usage characteristics
Usage characteristics
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Ambient ground temperature
20 °C
Laying operation bending radius
3300 mm
Laying depth, center of system
1000 mm
Laying tube diameter
200 mm
Distance between tubes (X)
300 mm