XDALT 1x150 Al/35 mm² 12/20 kV

Description

Description

Standards

  • Product
    HD 620; IEC 60502
  • National
    ASE

Applications

  • Underground distribution networks
  • Pipe laying and ground laying
  • Installation in electrical substations

Construction

  • Round copper or aluminium conductor
  • Extruded inner conductor
  • Cross-linked PE insulation (XLPE)
  • Extruded outer semi-conductor
  • Semi-conductive swelling tape
  • Laminated aluminium tape screen
  • Black PE outer sheath with 2 red longitudinal stripes

Properties

  • Longitudinal sealing by two layers of tapes which swell in the presence of moisture and prevent the spread of water in the event of an injury to the sheath
  • Radial sealing by means of the laminated aluminium tape
  • Special abrasion resistant PE outer jacket with low shrinkage rate
  • Cross-linked PE insulation (XLPE) with high dielectric strength and low losses
  • Halogen free

admissible load MV cables

 

Currents are indicative and given for normal service conditions.

  •  Permanent charge 24h at 100% LF =1.0
  • Conductor temperature 90 ° C

 

For cable laid in earth in tubes

  • Depth of laying in soil : 1.0 m
  • Max. soil temperatureempérature : 20 °C
  • Soil thermal resistivity: 1.0 °C m/W

 

For cables placed in the open air

  • Max. air temperature : 30 °C 
  • Protected from direct sunlight
  • laid on consoles or cable trays

  

Grounding:

  • at one end, in this case the induced voltage increases proportionally with the length of the
    the link.

    Attention, too high induced voltage can cause a breakdown of the outer sheath during overvoltages
    transient.

  • Either at both ends, which generates circulating currents and therefore more or less acceptable losses..

 

Correction factor

If the terms of service differ from those set out above, allowable currents must be corrected
taking into account all the correction factors that apply to the installation and service conditions encountered.


Main factors to consider are the following:

 

  • Variable load, factor taking into account variable load, 10h to 100% and 14h to 60% LF= 0.627
  • Operating temperature
  • Ambient Temperature
  • Thermal soil resistivity, factor taking into account the thermal resistivity of the soil in [°C * m / W]
  • Magnetic armor


Our engineers are at your disposal to help and advise you.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Class 2
Conductor material
Aluminum
Conductor shape
Round compacted

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
150 mm²
Conductor diameter
14.4 mm
Average insulation thickness
4.8 mm
Diameter over insulation
25.0 mm
Screen section
35 mm²
Diameter over external conductor / metallic screen
27.4 mm
Average sheath thickness
1.8 mm
Nominal outer diameter
31.0 mm
Approximate weight
100.6 kg/100m
Number of cores
1

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12/20 kV
Maximum operating voltage
24 kV
Max. DC resistance of the conductor at 20°C
0.206 Ohm/km
I max. @ 60°C-buried, flat, spaced, earthing 1pt, LF1
251 A
I max. @ 60°C-buried, flat, spaced, earthing 2pts, LF1
240 A
I max. @ 90°C-buried, flat, spaced, earthing 1pt, LF1
321 A
I max. @ 90°C-buried, flat, spaced, earthing 2pts, LF1
309 A
I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1
218.2 A
I max. @ 60°C-buried, trefoil, joined, earthing 2pts, LF1
230 A
I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1
280.8 A
I max. @ 90°C-buried, trefoil, joined, earthing 2pts, LF1
297 A
I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1
294.2 A
I max. @ 60°C-in the air inside, flat, spaced, earthing 2pts, LF1
304 A
I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1
419.2 A
I max. @ 90°C-in the air inside, flat, spaced, earthing 2pts, LF1
433 A
I max. @ 60°C-in the air inside, trefoil, joined, earthing 1pt, LF1
263 A
I max. @ 60°C-in the air inside, trefoil, joined, earthing 2pts, LF1
262 A
I max. @ 90°C-in the air inside, trefoil, joined, earthing 1pt, LF1
377 A
I max. @ 90°C-in the air inside, trefoil, joined, earthing 2pts, LF1
375 A
Permissible short circuit current conductor 0.5s
20.4 kA
Permissible short circuit current conductor 1s
14.5 kA
Permissible short circuit current screen 0.5s
4.7 kA
Permissible short circuit current screen 1s
3.4 kA
A.C. Conductor resist. 50Hz and at 90 °C
- Ohm/km
Nominal phase capacitance
0.281 µF / km
Nominal inductance
0.36 mH/km
Phase reactance 50 Hz - trefoil formation
0.114 Ohm/km
Impedance at 50Hz and 90°C
0.27 Ohm/km
Calorific Power
- MJ/m
I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627
235.2 A
I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627
303.4 A

Mechanical characteristics

Mechanical characteristics

Maximum pulling force by laying
4.5 kN

Usage characteristics

Usage characteristics

Bending factor when laying
15 (xD)
Bending factor when installed
9 (xD)
Minimum installation temperature
-5 °C
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Documentation

Declaration of Performance

  • Declaration of Performance n� : 1000390-CHCD
  • Certification Date : 3/1/23
  • AVCP (Assessment and Verification of Constancy of Performance) : System 4
  • Declared performance : Fca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close