XDALT-YT 3x1x 50 Cu/28 mm² 12/20kV

Description

Description

Standards

  • Product
    HD 620; IEC 60502
  • National
    ASE

Applications

  • Underground distribution networks
  • Pipe laying and ground laying
  • Installation in electrical substations

Construction

  • Round copper or aluminium conductor
  • Extruded inner conductor
  • Cross-linked PE insulation (XLPE)
  • Extruded outer semi-conductor
  • Semi-conductive swelling tape
  • Laminated aluminium tape screen
  • Black PE outer sheath, with 2 red longitudinal stripes
  • Three-pole construction:
  • Assembly of three monopolar cables
  • Outer sheath in HDPE

Properties

  • Longitudinal sealing by two layers of tape which swell in the presence of moisture and prevent the spread of water in the event of an injury to the sheath
  • Radial sealing provided by the laminated aluminium tape
  • Special abrasion resistant PE outer jacket with low shrinkage rate
  • Cross-linked PE insulation (XLPE) with high dielectric strength and low losses
  • Halogen free

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Round compacted

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
50 mm²
Conductor diameter
8.2 mm
Average insulation thickness
4.8 mm
Diameter over insulation
18.8 mm
Screen section
28 mm²
Diameter over external conductor / metallic screen
21.7 mm
Average sheath thickness
1.5 mm
Nominal outer diameter
57.9 mm
Approximate weight
291.2 kg/100m
Number of cores
3

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12/20 kV
Maximum operating voltage
24 kV
Max. DC resistance of the conductor at 20°C
0.387 Ohm/km
I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1
153 A
I max. @ 60°C-buried, trefoil, joined, earthing 2pts, LF1
152 A
I max. @ 60°C-in the air inside, trefoil, joined, earthing 1pt, LF1
172 A
I max. @ 60°C-in the air inside, trefoil, joined, earthing 2pts, LF1
172 A
I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1
197 A
I max. @ 90°C-buried, trefoil, joined, earthing 2pts, LF1
196 A
I max. @ 90°C-in the air inside, trefoil, joined, earthing 1pt, LF1
245 A
I max. @ 90°C-in the air inside, trefoil, joined, earthing 2pts, LF1
245 A
Impedance at 50Hz and 90°C
0.47 Ohm/km
Nominal inductance
0.43 mH/km
Nominal phase capacitance
0.201 µF / km
Permissible short circuit current conductor 0.5s
10.3 kA
Permissible short circuit current conductor 1s
7.4 kA
Permissible short circuit current screen 0.5s
3.3 kA
Permissible short circuit current screen 1s
2.4 kA
Phase reactance 50 Hz - trefoil formation
0.135 Ohm/km

Mechanical characteristics

Mechanical characteristics

Maximum pulling force by laying
6 kN

Usage characteristics

Usage characteristics

Minimum installation temperature
-5 °C
Bending factor when laying
12 (xD)
Bending factor when installed
8 (xD)
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Documentation

Declaration of Performance

  • Declaration of Performance n� : 1000391-CHCD
  • Certification Date : 3/1/23
  • AVCP (Assessment and Verification of Constancy of Performance) : System 4
  • Declared performance : Fca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close