Nexans XKDT-F Armoured 3 core cables XLPE insulated

Products

XKDT-F 3x1x 50/16 mm² 12/20 kV

Nexans ref. 10152593

  • Packaging: m
  • Conductor cross-section: 50 mm²

 

XKDT-F 3x1x 95/25 mm² 12/20 kV

Nexans ref. 10152596

  • Packaging: m
  • Conductor cross-section: 95 mm²

 

XKDT-F 3x1x150/35 mm² 12/20 kV

Nexans ref. 10152598

  • Packaging: Cut to length (m)
  • Conductor cross-section: 150 mm²

 

XKDT-F 3x1x240/35 mm² 12/20 kV

Nexans ref. 10199883

  • Packaging: m
  • Conductor cross-section: 240 mm²

 

Description

Description

Standards

  • Product
    HD 620; IEC 60502
  • National
    ASE

Applications

  • Underground distribution networks
  • Pipe laying and ground laying
  • Installation in electrical substations

Construction

  • Round copper or aluminium conductor
  • Extruded inner conductor
  • Cross-linked PE insulation (XLPE)
  • Extruded outer semi-conductor
  • Semi-conductive swelling tape
  • SZ concentric copper wire screen
  • Swelling tape
  • Black PE outer sheath, with 2 red longitudinal stripes
  • Three-pole construction:
  • Assembly of three monopolar cables
  • Extruded filler
  • Galvanised flat steel wire armouring

Properties

  • Longitudinal sealing by two layers of tapes which swell in the presence of moisture and prevent the spread of water in the event of an injury to the sheath
  • Outer jacket made of specially abrasion-resistant PE with a low shrinkage rate
  • Cross-linked PE insulation (XLPE) with high dielectric strength and low losses
  • Halogen free
  • Tensile armouring made of zinc-plated flat steel wires, suitable for installation on steep slopes or if mechanical protection of the cable is required

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular
Conductor flexibility
Stranded class 2
Insulation
XLPE (chemical)
Armour type
Galvanized flat steel wires (F)
Halogen free
Yes

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Maximum operating voltage
24 kV
Test voltage
48 kV
Impulse voltage
125 kV

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Documentation

Construction pdf — 297.1 kB

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close