XKDT 1x 50 Al/10 mm² 12/20 kV
XKDT 1x 50 Al/10 mm² 12/20 kV
Medium voltage 20 kV single-core cables with cross-linked PE insulation (XLPE) and copper-wire screen.
Read more- Nexans ref. : 10221202
- EAN : 7611755572372
Description
Description
Standards
-
ProductHD 620 S2 P10N; IEC 60228 Class 2 ; IEC 60502
Applications
- Underground distribution networks
- Laying in tubes and direct buried
- Arises in electrical substations
Key points
- Halogen free
- Outer PE sheath especially abrasion-resistant and low shrinkage
- Longitudinally watertight ensured by a tape which swells in the presence of moisture and prevent the spread of water in case of injury to the sheath
- XLPE cross-linked insulation high dielectric strength and low loss
Construction
- Aluminium conductor
- Inner semi-conductor extruded
- Cross-linked PE insulation (XLPE)
- Outer semi-conductor extruded
- Semi-conductive swelling tape
- Copper wire screen SZ
- Swelling tape
- Outer PE sheath black + 2 red lines
Notice
- Other cross-sections and voltage on request
- Noflamm sheath possible on request
admissible load MV cables
Currents are indicative and given for normal service conditions.
- Permanent charge 24h at 100% LF =1.0
- Conductor temperature 90 ° C
For cable laid in earth in tubes
- Depth of laying in soil : 1.0 m
- Max. soil temperatureempérature : 20 °C
- Soil thermal resistivity: 1.0 °C m/W
For cables placed in the open air
- Max. air temperature : 30 °C
- Protected from direct sunlight
- laid on consoles or cable trays
Grounding:
-
at one end, in this case the induced voltage increases proportionally with the length of the
the link.Attention, too high induced voltage can cause a breakdown of the outer sheath during overvoltages
transient. -
Either at both ends, which generates circulating currents and therefore more or less acceptable losses..
Correction factor
If the terms of service differ from those set out above, allowable currents must be corrected
taking into account all the correction factors that apply to the installation and service conditions encountered.
Main factors to consider are the following:
- Variable load, factor taking into account variable load, 10h to 100% and 14h to 60% LF= 0.627
- Operating temperature
- Ambient Temperature
- Thermal soil resistivity, factor taking into account the thermal resistivity of the soil in [°C * m / W]
- Magnetic armor
Our engineers are at your disposal to help and advise you.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Documentation
Declaration of Performance
- Declaration of Performance n� : 1000393-CHCD
- Certification Date : 3/1/23
- AVCP (Assessment and Verification of Constancy of Performance) : System 4
- Declared performance : Fca