Nexans XKDT-Y Alu XLPE insulated 3 core cables
Nexans XKDT-Y Alu XLPE insulated 3 core cables
Three-core cables with aluminium conductors, cross-linked PE insulation (XLPE), copper-wire screens and without outer protection sheath.
Conductor cross-sections of 95 mm² up to 400 mm².
Other voltage levels or conductor cross-sections on request.
Read moreXKDT-Y 3x1x150 Alrm / 25 CuK mm² 12/20kV
Nexans ref. 10195103
- Packaging: Cut to length (m)
- Conductor cross-section: 150 mm²
XKDT-Y 3x1x240 Alrm / 35 CuK mm² 12/20kV
Nexans ref. 10152612
- Packaging: Cut to length (m)
- Conductor cross-section: 240 mm²
XKDT-Y 3x1x400 Alrm / 35 CuK mm² 12/20kV
Nexans ref. 10557379
- Packaging: Cut to length (m)
- Conductor cross-section: 400 mm²
XKDT-Y 3x1x95 Alrm / 16 CuK mm² 12/20kV
Nexans ref. 10194925
- Packaging: Cut to length (m)
- Conductor cross-section: 95 mm²
Description
Description
Standards
-
ProductHD 620; IEC 60502
-
NationalASE
Applications
- Underground distribution networks
- Laying in tubes and direct buried
- Arises in electrical substations
Construction
- Aluminium conductor
- Inner Semiconductor
- Cross-linkend PE insulation (XLPE)
- Outer semi-conductor
- Semi-conductive swelling tape
- Copper wire screen
- Swelling tape
- Outer PE sheath
- Assembly of 3 XLPE insulated single core cables
Properties
- Longitudinal watertightness, which protects the cable against the spread of moisture in the event of damage to the sheath, is ensured by 2 swelling tapes
- PE outer sheath with increased abrasion resistance and low shrinkage rate
- Cross-linked PE insulation (XLPE) with dielectric strength and low dielectric losses
- Halogen-free
admissible load MV cables
Currents are indicative and given for normal service conditions.
- Permanent charge 24h at 100% LF =1.0
- Conductor temperature 90 ° C
For cable laid in earth in tubes
- Depth of laying in soil : 1.0 m
- Max. soil temperatureempérature : 20 °C
- Soil thermal resistivity: 1.0 °C m/W
For cables placed in the open air
- Max. air temperature : 30 °C
- Protected from direct sunlight
- laid on consoles or cable trays
Grounding:
-
at one end, in this case the induced voltage increases proportionally with the length of the
the link.Attention, too high induced voltage can cause a breakdown of the outer sheath during overvoltages
transient. -
Either at both ends, which generates circulating currents and therefore more or less acceptable losses..
Correction factor
If the terms of service differ from those set out above, allowable currents must be corrected
taking into account all the correction factors that apply to the installation and service conditions encountered.
Main factors to consider are the following:
- Variable load, factor taking into account variable load, 10h to 100% and 14h to 60% LF= 0.627
- Operating temperature
- Ambient Temperature
- Thermal soil resistivity, factor taking into account the thermal resistivity of the soil in [°C * m / W]
- Magnetic armor
Our engineers are at your disposal to help and advise you.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania