XKDT-YT 3x1x 95 Alrm / 16 CuK mm² 12/20kV
XKDT-YT 3x1x 95 Alrm / 16 CuK mm² 12/20kV
20 kV Three-core cable with aluminium conductors, cross-linked PE insulation (XLPE), copper-wire screens and triangular protection sheath.
Read more- Nexans ref. : 10152610
- EAN : 7611755206291
Description
Description
Standards
-
ProductHD 620; IEC 60502
-
NationalASE
Halogenfree three-core cables with aluminium conductors, cross-linked PE insulation ( XLPE), copper-wire screens and triangular protection sheath for medium voltage underground networks.
Applications
- Underground distribution networks
- Laying in tubes and direct buried
- Arises in electrical substations
Key points
- Nominal voltage 10 kV / 20 kV / 30 kV
- Lead sections 95 to 400 mm2
Construction three-core cables
- Assembly of 3 XLPE insulated single core cables
- Outer HDPE-sheath
Construction single core cables
- Aluminium conductor
- Inner Semiconductor
- Cross-linkend PE insulation (XLPE)
- Outer semi-conductor
- Semi-conductive swelling tape
- Copper wire screen
- Swelling tape
- Outer PE sheath
admissible load MV cables
Currents are indicative and given for normal service conditions.
- Permanent charge 24h at 100% LF =1.0
- Conductor temperature 90 ° C
For cable laid in earth in tubes
- Depth of laying in soil : 1.0 m
- Max. soil temperatureempérature : 20 °C
- Soil thermal resistivity: 1.0 °C m/W
For cables placed in the open air
- Max. air temperature : 30 °C
- Protected from direct sunlight
- laid on consoles or cable trays
Grounding:
-
at one end, in this case the induced voltage increases proportionally with the length of the
the link.Attention, too high induced voltage can cause a breakdown of the outer sheath during overvoltages
transient. -
Either at both ends, which generates circulating currents and therefore more or less acceptable losses..
Correction factor
If the terms of service differ from those set out above, allowable currents must be corrected
taking into account all the correction factors that apply to the installation and service conditions encountered.
Main factors to consider are the following:
- Variable load, factor taking into account variable load, 10h to 100% and 14h to 60% LF= 0.627
- Operating temperature
- Ambient Temperature
- Thermal soil resistivity, factor taking into account the thermal resistivity of the soil in [°C * m / W]
- Magnetic armor
Our engineers are at your disposal to help and advise you.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Documentation
Declaration of Performance
- Declaration of Performance n� : 1000399-CHCD
- Certification Date : 3/1/23
- AVCP (Assessment and Verification of Constancy of Performance) : System 4
- Declared performance : Fca