Nexans XKDT-YT XLPE insulated 3 core cables
Nexans XKDT-YT XLPE insulated 3 core cables
Three-core cables with cross-linked PE insulation (XLPE), copper-wire screens and triangular protection sheath.
Read moreXKDT-YT 3x1x 50 Cu/16 mm² 12/20 kV
Nexans ref. 10152594
- Packaging: m
- Conductor cross-section: 50 mm²
XKDT-YT 3x1x 95 Cu/25 mm² 12/20 kV
Nexans ref. 10152597
- Packaging: m
- Conductor cross-section: 95 mm²
XKDT-YT 3x1x150 Cu/35 mm² 12/20 kV
Nexans ref. 10152600
- Packaging: m
- Conductor cross-section: 150 mm²
XKDT-YT 3x1x240 Cu/35 mm² 12/20 kV
Nexans ref. 10152601
- Packaging: m
- Conductor cross-section: 240 mm²
XKDT-YT 3x1x300 Cu/35 mm² 12/20 kV
Nexans ref. 10170524
- Packaging: Cut to length (m)
- Conductor cross-section: 300 mm²
Description
Description
Standards
-
ProductHD 620; IEC 60502
-
NationalASE
Applications
- Underground distribution networks
- Pipe laying and ground laying
- Installation in electrical substations
Construction
- Round copper or aluminium conductor
- Extruded inner conductor
- Cross-linked PE insulation (XLPE)
- Extruded outer semi-conductor
- Semi-conductive swelling tape
- SZ concentric copper wire screen
- Swelling tape
- Black PE outer sheath, with 2 red longitudinal stripes
- Three-pole construction:
- Assembly of three monopolar cables
- HDPE outer sheath
Properties
- Special abrasion resistant PE outer jacket with low shrinkage rate
- Cross-linked PE insulation (XLPE) with high dielectric strength and low losses
- Halogen free
admissible load MV cables
Currents are indicative and given for normal service conditions.
- Permanent charge 24h at 100% LF =1.0
- Conductor temperature 90 ° C
For cable laid in earth in tubes
- Depth of laying in soil : 1.0 m
- Max. soil temperatureempérature : 20 °C
- Soil thermal resistivity: 1.0 °C m/W
For cables placed in the open air
- Max. air temperature : 30 °C
- Protected from direct sunlight
- laid on consoles or cable trays
Grounding:
-
at one end, in this case the induced voltage increases proportionally with the length of the
the link.Attention, too high induced voltage can cause a breakdown of the outer sheath during overvoltages
transient. -
Either at both ends, which generates circulating currents and therefore more or less acceptable losses..
Correction factor
If the terms of service differ from those set out above, allowable currents must be corrected
taking into account all the correction factors that apply to the installation and service conditions encountered.
Main factors to consider are the following:
- Variable load, factor taking into account variable load, 10h to 100% and 14h to 60% LF= 0.627
- Operating temperature
- Ambient Temperature
- Thermal soil resistivity, factor taking into account the thermal resistivity of the soil in [°C * m / W]
- Magnetic armor
Our engineers are at your disposal to help and advise you.
Characteristics
Characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania