FE0-D-CLN 5X50 RM SW 3LNPE

Description

Description

Standards

  • Product
    EN 50575; EN 60529; IEC 60228
  • Test
    EN 60332-1-2; EN 60754-2; IEC 61034
  • National
    SEV TP 20B/3C-d

Applications
Halogen-free installation cable with armouring for installation in buildings and equipment rooms. The light steel armouring protects the cable from rodents. This type of cable has been used for years in railway and motorway projects.

 

Construction

  • Conductor Wire (class 1) of 1.5 - 6mm2 and ropes (class 2) of 10 - 630mm2
  • Polyethylene insulation
  • Filling : yes
  • Double steel tape armouring
  • Black HFFR sheath

Properties

  • CPR Class Dca s2, d2, a2
  • Water resistant. Up to two months immersion (AD7)
  • Halogen-free allows a higher level of safety than PVC TT cables

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Armour type
Steel tapes
Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Round compacted
Halogen free
Yes
Insulation
PE
Outer sheath
HFFR (Halogen Free Flame Retardant)
Sheath colour
Black

Dimensional characteristics

Dimensional characteristics

Number of cores
5
Conductor cross-section
50 mm²
Approximate weight
3494 kg/km
Nominal outer diameter
39.3 mm

Electrical characteristics

Electrical characteristics

Maximum operating voltage
1000 V
Rated Voltage Uo/U (Um)
0,6/1 kV
Test voltage
3500 V

Usage characteristics

Usage characteristics

Fire load
- MJ/km
Flame retardant
IEC 60332-1-2
Maximum operating temperature
70 °C
Minimum operating temperature
-20 °C
RoHS conform
-
Smoke density
EN 50399
U.V resistance
Yes
Water proof
AD7
Weather resistance
Good

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1000759-CHCD
  • Certification Date : 3/1/23
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 81
  • Declared performance : Dca-s2,d2,a2

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close