AMV-M-MAKY24.0/3X1X025-150S(1)
AMV-M-MAKY24.0/3X1X025-150S(1)
Einleiter - Verbindungsmuffe, Kaltschrumpftechnik
Mehr lesen- Nexans ref. : 10216665
Beschreibung
Beschreibung
Normen
-
TestsHD 629.1 S2
Application
- To connect single core polymeric cables, aerial or underground
- For cables with copper or aluminium conductor
Technical description
- Extruded joint body
- Extruded protection sheath
- Cable lugs with large usage range for copper and aluminium conductor
- Semiconductive watertight putty
- Metallic screen
Remarks
- Premounted joint, factory tested
- Cable lugs for conductors and screens
- Multi-lingual mounting instructions
Characteristics
- Compact joint with short overall length
- Low space requirements for installation
- Easy installation
- No specific tools required
Eigenschaften
Eigenschaften
Konstruktionsmerkmale
Konstruktionsmerkmale
Leitermaterial
Kupfer oder Aluminium
Abschirmung
Copper wires / 6mm²
Leiterisolationsmaterial
Synthetic
Technologie
Kaltschrumpf
Anzahl Leiter
1
Kabeltyp
Dreileiter XKDT, XDCuT
Abmessungen
Abmessungen
Aussendurchmesser maximal
150.0 mm
Länge L
1200.0 mm
Durchmesser über Isolation, Bereich
17 ... 38 mm
Approximatives Gewicht pro Set
8 kg
Leiterquerschnitt, Bereich
25 ... 150 mm²
Elektrische Eigenschaften
Elektrische Eigenschaften
Nominale Betriebsspannung Uo/U
12 / 20 (24) kV
Stosshaltespannung
125 kV
Spannungsprüfung, 50Hz 1min
55 kV
Anwendungsmerkmale
Anwendungsmerkmale
Einsatzbereich
Innen- und Ausseninstallationen, erdverlegt
Umgebungstemperatur bei Installation
5 ... 40 °C
Spannungsklasse
24 kV
Verpackung
Set zu 3 Stück
Unsere Websites