AMV-M-MAEK36.3/1X185-400S(1)
AMV-M-MAEK36.3/1X185-400S(1)
Einleiter - Verbindungsmuffe, Kaltschrumpftechnik
Mehr lesen- Nexans ref. : 10511136
Beschreibung
Beschreibung
Normen
-
TestsHD 629.1 S2
Application
- To connect single core polymeric cables, aerial or underground
- For cables with copper or aluminium conductor
Technical description
- Extruded joint body
- Extruded protection sheath
- Cable lugs with large usage range for copper and aluminium conductor
- Semiconductive watertight putty
- Metallic screen
Remarks
- Premounted joint, factory tested
- Cable lugs for conductors and screens
- Multi-lingual mounting instructions
Characteristics
- Compact joint with short overall length
- Low space requirements for installation
- Easy installation
- No specific tools required
Eigenschaften
Eigenschaften
Konstruktionsmerkmale
Konstruktionsmerkmale
Leitermaterial
Kupfer oder Aluminium
Abschirmung
Alu- oder Kupferbandschirm
Leiterisolationsmaterial
Synthetic
Technologie
Kaltschrumpf
Anzahl Leiter
1
Kabeltyp
Einleiter XDCuT
Abmessungen
Abmessungen
Aussendurchmesser maximal
88.0 mm
Länge L
850.0 mm
Durchmesser über Isolation, Bereich
30 ... 50 mm
Approximatives Gewicht pro Set
9 kg
Leiterquerschnitt, Bereich
185 ... 400 mm²
Elektrische Eigenschaften
Elektrische Eigenschaften
Nominale Betriebsspannung Uo/U
18 / 30 (36) kV
Stosshaltespannung
170 kV
Spannungsprüfung, 50Hz 1min
75 kV
Anwendungsmerkmale
Anwendungsmerkmale
Einsatzbereich
Innen- und Ausseninstallationen, erdverlegt
Umgebungstemperatur bei Installation
5 ... 40 °C
Spannungsklasse
36 kV
Verpackung
Set zu 1 Stück
Unsere Websites
Wählen Sie Ihr Land aus, um unsere Produkte und Lösungen zu finden
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania